Standard SANITARY FITTINGS



TYPE DESCRIPTION

1. Wash Basins (a) 560mm x 410mm wash basin in approved colour vitreous china complete with
                             chromium plated tap, blank tap hole stopper, 30mm ‘p’ or ‘s’ trap with
                             40mm seal, waste fittings, plug with chain and painted bracket supports.
                        (b) Ditto, but with two chromium plated tap, marked ‘hot’ and ‘cold’ (for cold
                             and hot water supply only).



2. Vanity Tops   (a) Vanity top as specified, with integrated sink as shown in the Drawings,
                                complete with chromium-plated tap, blank tap hole stopper, 30mm ‘p’
                                or ‘s’ trap with 40mm seal, waste fittings and plug with chain.
                          (b) Vanity top as specified, but with holes pre-punched to receive an
                                under-counter vanity basin and tap respectively, as shown in the
                                Drawings, complete with 555mm x 415mm under-counter vanity basin in
                                vitreous china, complete with chromium-plated tap, 30mm ‘p’ or ‘s’ trap
                                with 40mm seal, waste fittings and plug with chain, and painted
                                bracket supports.




3. Sink               (a) 600mm x 400mm x 200mm earthenware plain edge sink in white fireclay
                               complete with chromium plated tap, 40mm ‘p’ or ‘s’ trap with 40mm seal,
                               waste fittings, plug with chain and painted cast iron brackets.
                          (b) Metal sinks in stainless steel to size and shape as shown in the
                               Drawings, complete with chromium plated tap as required, 40mm ‘p’ or
                               ‘s’ trap with 40mm seal, waste fittings, plug with chain and painted cast
                               iron supports.

4. Water Closet    (a) Pedestal closet in white vitreous china conforming to MS 1522:2001 or
                                JKR Standard Specification 20200-0110-01 complete with pedestal pan,
                                ‘p’ trap and ventilation outlet, plastic hinged seat and rubber buffers.
                           (b) Squatting closet in white vitreous china conforming to MS 1522:2001 or
                                JKR Standard Specification complete with pair of raised
                                 foot treads in white fire clay with ‘p’ trap and 40mm diameter uPVC flush
                                 pipe.




5. Urinals            (a) Single urinal bowl in white vitreous china conforming to JKR Standard
                              Specification complete with back
                              inlets, hangers and steadying brackets, 40mm outlet with hinged
                              gratings and 50mm uPVC waste pipe.
                         (b) Urinal range of 2 or more bowls as (a) but with white vitreous china
                              division between bowls.
6. Cistern for       (a) All W/C Cisterns shall be low pressure or Type B flushing cisterns
                               water closet conforming to JKR Standard Specification.
                          (b) Single flush 6 litres or dual-flush 6 / 3 liters low level vitreous china
                               Urinal flushing cistern in white vitreous china
                               conforming to JKR Standard Specification complete with
                               chromium plated flushing inlet pipe, 20mm diameter overflow for
                               discharge externally and chrome lever handle.


8. Flush valve for    (a) W/C flush valve shall be low pressure single flush 6 litres gravity flush
                                     water closet valve. It shall have a non-hold-open feature or an automatic shut-off
                                     system. Vacuum Breaker is optional, only applicable to w/c flush valves
                                     intended to be connected to direct potable water mains. It’s performance
                                     requires proper match of valve and w/c pan conforming to MS 1522:01.

                                 (b) Each flush valve shall be made of metal (preferably copper alloy) and
                                      corrosion resistant. All exposed surfaces to the users shall be chromed
                                      plated or made of stainless steel.
                                  (c) Each water closet flush valve used shall comply fully with ASSE
                                      1037:1990, performance requirements for Pressurized Flushing Devices
                                      (Flush meters) for Plumbing Fixtures. Testing and certification by other
                                      approved testing body may be allowed with the S.O’s approval. Each
                                      flush valve together with w/c shall pass all the tests listed below:
                                                  i) Endurance test;
                                                  ii) Hydraulic test;
                                                  iii) Performance tests according to test methods stipulated in MS
                                                      1522:01
                                                       a) Newspaper test;
                                                       b) Simulating solid test; 
                                                       c) Sawdust test and 
                                                       d) Ball test



9. Flush valve for       (a) Urinal flush valve shall be Single flush 2.5 litres gravity flush valve.
                                    urinal It shall have a non-hold-open feature or an automatic shut-off system.
                               (b) Each urinal flush valve shall be made of metal (preferably copper alloy)
                                    and corrosion resistant. All exposed surfaces to the users shall be
                                    chromed plated or made of stainless steel.
                                (c) Each urinal flush valve shall be tested as stipulated in the requirements
                                     of JKR Standard Specification or AS 3982:1996.
                                     (OTHERS: state if required)






























( NOTES: SOME OF COMPANY OR SECTOR MAYBE DIFFERENT OF LOG SHEET TEST )
( HERE SOME OF USEFUL EXAMPLE OF TEST LOG SHEET FOR INFORMATION ONLY )




Pressure Test Log Sheet

Project: 



__________________________________( NAME OF THE PROJECT )__________________________________
___________________________________________________________________


(A) For Plastic Pipes ( uPVC pipes, PE pipes, ABS pipes, PB pipes, PP-R Type 3 pipes etc)

I. Preliminary Test

Test begin at ____________(at least 15 bar) (a) _____________ bar
Pressure after 30 minutes (b) _____________ bar
Pressure after 60 minutes (c) _____________ bar*1
*1 - shall not be more than 0.6 bar after 30 minutes
Leakage 9 yes 9 no

II. Main Test

Start after preliminary test completed _________ (c) _____________ bar

Pressure after 120 minutes (d) _____________ bar*2

*2 - shall not be more than 0.2 bar
Leakage 9 yes 9 no

(B) For Metal Pipes ( stainless steel pipes, copper pipes etc)


Test begin at __________( at least 15 bar) (a) _____________ bar
Pressure after 30 minutes (b) _____________ bar
Leakage 9 yes 9 no

Installer/Company:

Date: _______________ Completed by: ________






( NOTES: SOME OF COMPANY OR SECTOR MAYBE DIFFERENT )
( HERE SOME OF USEFUL EXAMPLE OF TEST LOG SHEET FOR INFORMATION ONLY )

Note: separate system for top floor 


TYPICAL SCHEMATIC DIAGRAM OF INTERNAL PLUMBING FOR LOW PRESSURE FLUSHING
CISTERNS, WASH BASIN TAPS AND W/C TAPS FOR A FOUR-STOREY BUILDING




( NOTES: SOME OF COMPANY OR SECTOR MAYBE DIFFERENT )
( HERE SOME OF USEFUL EXAMPLE OF TEST LOG SHEET FOR INFORMATION ONLY )

Note: separate system for top floor 


2 Responses so far.

  1. Anonymous says:

    salam en adi,saya tengah kaji pasal JKR standards utk valves. En adi tahu tak macam mana nak dapatkan standard tu?

  2. Your blog has given me that thing which I never expect to get from all over the websites. Nice post guys!
    regards,
    airless spray gun

Leave a Reply

comment.....?

MY SUPERB, AMAZED, MARVELOUS ECE SUPPORT......


ShoutMix chat widget